PREDICTION OF TRANSIENT INSTABILITY ON 132KV TRANSMISSION GRID POWER SYSTEM USING TRAPEZOIDAL RULE.

Domaine:

environment and energy

Type de record:

paper
Créateur:
Chi
Éditeur:
Eth
Hôte:avatar
This paper deals with prediction of transient instability on 132kV grid network from Afam to Port Harcourt mains injection substation in Nigeria by determining the dynamic response of the generators on the system during fault conditions using Trapezoidal numerical technique.  The network’s data collected from Transmission Company of Nigeria were used as input to perform transient stability simulation in Electrical Transient Analyzer Program (ETAP 19.1) environment, so as to investigate the differential change in generator rotor angles, change in generator bus voltage and frequency of the system. Numerical techniques were deployed with circuit breaker and relay time setting (0.00, 0.02, 0.04, 0.06, 0.08, 0.10, 0.12, 0.14, 0.16, and 0.18.0.2s), when balanced 3 phase fault was initiated with the aim of determining the critical clearing angle (CCA) and critical clearing time (CCT) of the transmission grid. The results obtained shows that Trapezoidal rule numerical technique is stable, accurate, has a fast response time of 0.02s, lower percentage error of 5.6% and a stable critical clearing angle of 35.480. The Trapezoidal rule numerical technique is better when used compared to modified Euler method in sustaining stability during transient disturbance to the network under investigation when in operation

Visit

doi.orgzenodo.org

Tags

Transient Instability, Modified Euler, ETAP, Trapezoidal rule, Critical Clearing Angle, Critical Clearing Time

Licenses

Creative Commons Attribution 4.0 Internationalhttps://creativecommons.org/licenses/by/4.0/legalcode

Similaires

Artificial Neural Networks-Based HVDC System for Transient Stability Enhancement of Nigeria Power GridDynamic Stability Control of Sudan National Grid Using Power System StabilizerLOAD FLOW ANALYSIS OF 132KV CALABAR TRANSMISSION SYSTEM FOR IMPROVED PERFORMANCE USING GLOBAL BEST ARTIFICIAL BEE COLONY (GABC) ALGORITHMPrediction of Photovoltaic Power Injected into the Grid Using Artificial Intelligence Algorithm: Case of Ten Merina Power Plant, SenegalInfluence of increasing Integration of Solar photovoltaic on Small Signal and Transient stability of Nigeria Power SystemHarnessing Excess Transmission Power for Grid Stability in Nigeria

Artificial Neural Networks-Based HVDC System for Transient Stability Enhancement of Nigeria Power Grid

Abstract The increasing disturbances in power system networks present significant challeng

Dynamic Stability Control of Sudan National Grid Using Power System Stabilizer

Application of power system stabilizers (PSS), as supplementary control signals for the excitation s

LOAD FLOW ANALYSIS OF 132KV CALABAR TRANSMISSION SYSTEM FOR IMPROVED PERFORMANCE USING GLOBAL BEST ARTIFICIAL BEE COLONY (GABC) ALGORITHM

Load flow analysis plays an important role in the planning, operation, optimization and control of a

Prediction of Photovoltaic Power Injected into the Grid Using Artificial Intelligence Algorithm: Case of Ten Merina Power Plant, Senegal

Influence of increasing Integration of Solar photovoltaic on Small Signal and Transient stability of Nigeria Power System

Abstract In this paper, the effect of Solar Photovoltaic (SPV) penetration on th

Harnessing Excess Transmission Power for Grid Stability in Nigeria

The Nigerian electricity network, with an average generation capacity of 5500 MW, face significant c